Application Scope:
LSZH cable available for the LSZH condition in case of ?re hazard. Used for device in kitchen, of?ce, and indoor damp location. In cause of no connection of heating parts or heating radiation, available for cooking and heating device. Not available for wiring of high temperature environment(such as lighting device), outdoor, industry & agriculture building, power tools.
Structure:
Conductor: Stranded bare copper or tinned copper in accordance with VDE 0281 Part 5, HD21. BS 6360 cl. 5, IEC 60228 cl. 5, HD 383
Insulation: Thermoplastic compound TI6 in accordance with DIN VDE 0281
Color recognition: Color code accordance with VDE-0293-308
Jacket Material: halogen-free Thermoplastic compound
Application standard: <HAR> HD21.14 S1, VDE-0281 Part-14, VDE 0482-332-1-2, CEI 20-20/14, CEI 20-35 (EN60332-1), CEI 20-37 (EN50267), EN50363, CE Low voltage 73/23/EEC & 93/68/EE
Characteristics and Conformity:
Features: Super ?ne conductor, ?exible for small bending angle Durable for certain external mechanical forces
Smoke density: EN 50268 / IEC 61034
Fire resistance test standard: EN 50265-2-1, IEC 60332.1 In accordance with EU coordination standard
Conformity Approval: RoHS CE
Technical Parameters:
Rated Voltage: 300/300V(H03Z1Z1-F); 300/500V(H05Z1Z1-F)
Test Voltage: 2000V(H03Z1Z1-F), 2500V(H05Z1Z1-F) HD21.2 In accordance with DIN VDE 0281 Part 2 HD21.2
Min. Bending Radius
Fixed Installation: 5¡ÁD (Cable OD)
Movable Installation: 8¡ÁD (Cable OD)
Temperature Range
Fixed Installation: -20 To +70¡æ
Movable Installation: -5 To +70¡æ